5.2 Client Side Connection Parameters
Specify which port the device is connected to the
FieldServer
nfs2-nca; nca2; nfs2-3030
CRT Port
4800; 9600; 19200; 38400; 57600; (Vendor
limitation)
Printer Port
9600 (Vendor limitation)
Example
// Client Side Connections
5.3 Client Side Node Parameters
Up to 32 alphanumeric characters
Station address of any physical Node on
network
1-240. Set unique Id for standalone Notifer-
3030 Panel
nfs2-nca or nca2 ; nfs2-3030
Specify which port the device is connected
to the FieldServer
Example
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.