: suppo[email protected] 5.3 Client Side Map Descriptor Parameters
5.3.1 FieldServer Related Map Descriptor Parameters
Name of this Map Descriptor
Up to 32 alphanumeric characters
Name of Data Array where data is
to be stored in the FieldServer
One of the Data Array names from Section 4
Starting location in Data Array
0 to (Data_Array_Length -1) as specified in Section
4
Function of Client Map
Descriptor.
Wrbc, Wrbx, Rdbc, Arcs. Refer to Error! Reference
source not found. for more information.
5.3.2 Driver Related Map Descriptor Parameters
Name of Node to fetch data from
One of the Node names specified in
“Client Node Descriptor” above
Specify memory area. Refer to Appendix
A.1.2 on how to transfer 32 Bit values
using Modbus registers.
Coil, Discrete_Input, Input_Register,
Holding_Register, Single_Coil,
Single_Register, Slave_Id
FC01, FC02, FC03, FC04,
FC05, FC06, FC15, FC16
Address_Type = Modicon_5digit
- (Dash), Single_Register, Single_Coil
Float_Reg, 32-Bit_Reg, Input_Float,
Input_Reg_32Bit
Starting address of read block
Address_Type = Modicon_5digit
Length of Map Descriptor.
1-125 (For Analog polls),
1-800 (For Binary polls).
Set to Map Descriptor Length if write-thru
operation should write all registers as
specified by length parameter.
By default write-thru writes a single
register.
Map Descriptor Length, 1,
Scaling zero in Data Array
Any signed 32 bit integer in the range:
Optional only for Modicon_5digit addressing, and only if Single writes do not need to be forced